Features
- 7 isolated outputs 24 V DC with up to 10 A each
- 40 A in total, briefly (10 s) 60 A
- Separate fuse and power measurement per output
- Backup via external 36 V battery
- DIN rail mounting, 18 modules
Note
As a battery we recommend our battery module BM3612-01.
AC input (mains voltage)
| Rated voltage | 208 … 240VAC, 50 … 60Hz |
|---|---|
| Input current rated / peak | 4.6A / 6.9A |
| Inrush current | 15A |
| Efficiency | typ. 94% |
| No-load power consumption | 4W |
| Power factor | 0.96 |
DC outputs
| Rated voltage | 24 … 27VDC (adjustable in LOXONE Config) |
|---|---|
| Total current rated load (continuous) | Mains operation: 40A Battery operation: 25A |
| Total current peak load (10sec) | Mains operation: 60A Battery operation: 40A |
| Output design | 7 outputs with up to 10A each individually fused, user-replaceable fuses Indication of defective fuses via LEDs and software Power measurement for each output isolated from mains, SELV and PELV capable GND terminals internally connected Thermal and overload protection by switching off the total load |
| Fuse type | Automotive blade fuse mini 32V, APM/ATM Littelfuse® 297 max. 15A |
Battery input
| Rated voltage | 36VDC |
|---|---|
| Discharge current peak load | 25A |
| Discharge current rated load | 17A |
| Max. charging current | 2A |
| Battery type | Lead-acid, VRLA recommended |
| Battery capacity | max. 200Ah for a single battery of a 36V pack |
| Max. length of battery cables | 2m / 6.56ft |
| Battery fusing | The battery cable must be suitably fused close to the battery. |
Interfaces
| LOXONE Tree | Connection to Miniserver / Tree Extension |
|---|
Ambient conditions
| Ambient temperature | -25 … 70°C / -13 … 158°F Derating of 2% / °K above 45°C / 113°F required! |
|---|---|
| Humidity | max. 95 % RH (non-condensing) |
| Installation | Mount on a DIN rail in a suitable installation distribution board. Ensure heat dissipation by mounting horizontally in the lower part of the distribution board with a clearance of 50mm / 2″ above and below the device. Do not cover ventilation openings. |
| Min. volume of the distribution board | 100l / 6100 cu in |
Connection terminals
| Terminal type | AC input, DC Outputs: 2EDGK Battery input: EC762V LOXONE Tree: DG220B |
|---|---|
| Stripping length | AC input, DC Outputs: 7mm / 0.28″ Battery input: 8mm / 0.32″ LOXONE Tree: 5 … 6mm / 0.2 … 0.24″ |
| Tightening torque | AC input, DC Outputs: 0.5 … 0.6Nm / 0.37 … 0.44 lbf ft Battery input: 0.7Nm / 0.52 lbf ft LOXONE Tree: – |
| Temperature resistance | AC input, DC Outputs: min. 90°C / 194°F Battery input: min. 90°C / 194°F LOXONE Tree: -40 … 105°C /-40 … 221°F |
Electrical specifications
| Degree of protection | PELV recommended |
|---|
Product properties
| Mounting type | DIN rail according to EN 50022, 35 mm |
|---|---|
| Colour | Black: RAL 9005 |
| Gloss level | Matt |
Weight & dimensions
| Net weight | 1532g |
|---|---|
| Gross weight | 1832g |
| Product dimensions | 324x110x72.37mm / 12.76×4.33×2.85″ (LxWxH), 18 modules |
| Package dimensions | 372x148x105mm / 14.65×5.83×4.13″ (LxWxH) |
Product dimension drawing

Certifications & standards
| Protection class | IP20 |
|---|---|
| Area of application | Type 1 (with protective earth, built-in device for fixed wiring) |
| Pollution degree | 2 |
| Overvoltage category | II, according to IEC 62368-1 |
| EMC complies with the following standards | EN 61000-6-1 EN 61000-6-3 |
Derating