Features
- Set with three split-core current transformers
- Measuring range primary 100 A / secondary 40 mA
- Opening: 16 mm
- Accuracy class: 0.5
- Colour-coded cable (5 m, can be shortened to 1 m)
- Integrated cable tie holder
- Clear direction marking
Note
Suitable for the Loxone Energy Meter for 40mA Current Transformers Tree.
Electrical specifications
| Rated primary current | 100 A |
|---|---|
| Rated secondary current | 40 mA |
| Accuracy class | 0.5 |
| Rated burden | 3.9 Ohm |
| Operating frequency | 50/60 Hz |
| Linear measuring range | 5 … 120 % of the measuring range on the primary side |
| Measuring error at rated primary current | ± 0.5% |
| Phase error at rated primary current | < 60' |
Insulation & safety
| Dielectric strength at mains frequency | 4 000 V / 10 s, 1 mA |
|---|---|
| Insulation resistance | 100 MOhm @ 500 VDC |
| Housing flame retardancy class | UL 94-V0 |
| Open-circuit protection voltage | 6 … 8 V |
Ambient conditions
| Temperature | -40 … 55 °C / -40 … 131 °F |
|---|---|
| Storage temperature | -40 … 85 °C / -40 … 185 °F |
| Humidity | max. 95 % RH (non-condensing) |
| Degree of protection | IP40 |
| Atmospheric pressure conditions | 70 … 106 kpa |
Secondary output cable
| Conductor cross-section | 0.5 mm² / AWG 22 |
|---|---|
| Length | 5 m (can be shortened to 1 m) |
| Wire ends | tinned wire ends (5 … 10 mm) |
Wiring diagram

Weight & dimensions
| Net weight | 524 g |
|---|
Product dimension drawing

Certifications & standards
| Certifications | UL E549933 |
|---|