Features
- Easy setup: seamless integration via Tree – no Modbus configuration required
- MID certified & ANSI accuracy class 0.5
- Only 2 modules: half the size of conventional meters
- Keep track: cost and consumption control
- Live readings: captures even short load peaks with updates every second
- Safe: fully integrated into load management
- Save money: optimised for energy management through live monitoring
- Display on the device: shows the current power and the total meter reading
- Fail-safe: detects grid failures immediately via dual DC/AC power supply
- Flexible choice: adapts to your installation – configurable primary currents from 5 to 9999 A
- Bidirectional energy measurement
Note
Matching current transformers are required: 40mA current transformer 100A 16mm or 40mA current transformer 25A 10mm.
Supply and power
| Voltage | AC (mains): 100 … 480 VAC, 50/60 Hz 24 VDC: 10 … 30 VDC |
|---|---|
| Power consumption | AC: ≤ 0.6 W 24 VDC: < 0.2 W |
| Power loss at max. load | AC: ≤ 2 W 24 VDC: 0.3 W |
Measuring range
| Power | Range: 0.01 … 999.9 kW / kVAr / kVA Accuracy: ± 1 % |
|---|---|
| Energy | Range: 0 … 999,999.9 kWh / kVArh Consumption and delivery Accuracy: class 2 IEC 62053, class C EN 50470 |
| Voltage | Range: 100 … 277 VAC Accuracy: ± 0.5 % |
| Current (transformer secondary) | Range: 0.4 … 48 mA Accuracy: ± 0.5 % |
| Frequency | Range: 45 … 60 Hz Accuracy: ± 0.2 % |
| Supported primary current | 5 … 9999 A |
| Grid systems | 3P4W, 1P3W, 3P3W |
| Measuring range of transformers | 25 A transformers: 1.25 … 30 A 100 A transformers: 5 … 120 A |
Operating conditions according to MID 2014/32/EU Annex V
| Voltage | Un: 3 × 230 / 400 VAC, ± 20 % |
|---|---|
| Current | Imin: 0.4 mA / Iref: 40 mA / Imax: 48 mA |
| Frequency | fn: 50 Hz, ± 2 % |
| Power factor | cos φ: 0.5 inductive … 0.8 capacitive |
| Accuracy (energy) | Class C (0.5 %, at +5 … +30 °C) |
Interfaces
| Loxone Tree | Connection to Miniserver / Tree Extension |
|---|
Ambient conditions
| Temperature | -40 … 70 °C |
|---|---|
| Humidity | max. 90 % RH (non-condensing) |
| Degree of protection | IP20 |
Terminals
| Terminal type | DG220B |
|---|---|
| Conductor cross-section | Current & voltage inputs: 0.5 … 1.5 mm² (wire end ferrules for fine-stranded conductors) 24 VDC & Loxone Tree: 0.28 … 0.8 mm² |
| Stripping length | Current & voltage inputs: 6 … 7 mm 24 VDC & Loxone Tree: 5 … 6 mm |
| Tightening torque | Current & voltage inputs: 0.6 Nm |
| Screwdriver | Slotted 0.5 × 3.5 mm |
Product properties
| Mounting type | DIN rail according to EN 50022, 35 mm |
|---|---|
| Colour | Black: RAL 9005, matte |
Weight & dimensions
| Net weight | 145 g |
|---|---|
| Gross weight | 167 g |
| Product dimensions | 36 × 100 × 66 mm (L × W × H), 2 modules |
| Package dimensions | 120 × 70 × 40 mm (L × W × H) |
Certifications & standards
| MID | certified |
|---|---|
| Accuracy class | 0.5 (ANSI C12.1) |