Touch Pure Flex CO2 Tree: operation and air quality in one place
This version is worthwhile in rooms where the air quickly becomes stale: bedrooms, children’s rooms, offices or meeting rooms. The sensor works between 10 and 50 °C at 10 to 90 % relative humidity; the Miniserver uses it to control a ventilation system or to remind you to open the window.
Without CO2 measurement there is the Touch Pure Flex Tree. For rooms without a Tree cable, the Touch Pure Flex 24V CO2 Air is the wireless version.
How can you design your Touch?
- Go to the page: https://configurator.loxone.com/
- Configure your custom Touch Flex there.
- Then click the “Share” button at the top of the Configurator.
- A link will then appear.
- Paste this link into the field on this product page and you will receive your personal custom Touch Flex within 2–3 weeks.
The Touch Flex is custom-made to order and is therefore excluded from returns.
Electrical specifications
| Supply voltage | 9 … 28 V DC |
|---|---|
| Power consumption | Standby: 0.2 W, max. 0.9 W at 100 % brightness |
Interfaces
| LOXONE Tree | Connection to Miniserver / Tree Extension |
|---|
Controls
| Touch area | capacitive touch detection up to 12/14 touch points |
|---|---|
| Click feedback | Yes |
| Backlight | Yes |
Measuring range
| Temperature | -10 … 125 °C ± 0.5 °C / -14 … 257 °F ± 0.9 °F |
|---|---|
| Humidity | 0 … 100 % RH ± 2 % (non-condensing) |
| CO2 | 400 … 5,000 ppm ( ± 100 ppm, ± 10 % of the measured value) |
Ambient conditions
| Temperature | -20 … 40 °C / -4 … 104 °F |
|---|---|
| Humidity | max. 95 % RH (non-condensing) |
| Degree of protection | IP20 |
| Operating conditions of the CO2 sensor | Temperature: 10 … 50 °C / 50 … 122 °F Humidity: 10 … 90 % RH (non-condensing) Max. dew point: 35 °C / 95 °F Air pressure: 850 … 1,100 hPa Within the first 12 hours after switching on, the CO2 sensor calibrates itself automatically for the first time. During this time the sensor values may be inaccurate. The CO2 sensor calibrates itself over time, provided it is exposed to fresh air (~400 ppm CO2) at least once a week. |
Installation specifications
| Recommended mounting height | 135 cm / 53.15″ |
|---|
Terminals
| Terminal type | DG220B |
|---|---|
| Conductor cross-section | 0.28 … 0.8 mm² / AWG 23 … 18 |
| Stripping length | 5 … 6 mm / 0.2 … 0.24” |
| Temperature resistance | -40 … 105 °C / -40 … 221 °F |
Product properties
| Colour | Signal white (RAL 9003) |
|---|---|
| Gloss level | Matt |
Weight & dimensions
| Net weight | 100 g |
|---|---|
| Gross weight | 142 g |
| Product dimensions | 90 x 90 x 16 mm / 3.55 x 3.55 x 0.63” (L x W x H) |
| Package dimensions | 104 x 107 x 39 mm / 4.09 x 4.21 x 1.54” (L x W x H) |
Product dimension drawing

Certifications & standards
| Standards | IEC 62368-1:2018UL 62368-1:2019 Ed. 3+R:22Oct2021CSA C22.2 No. 62368-1:2019 Ed. 3+U1SASO IEC 62368-1:2020 |
|---|
Connections