Features
- Easy setup: seamless integration via Tree – no Modbus configuration required
- MID certified & ANSI accuracy class 0.5
- Only 2 modules: half the size of conventional meters
- Keep track: cost and consumption control
- Live readings: captures even short load peaks with updates every second
- Safe: fully integrated into load management
- Save money: optimised for energy management through live monitoring
- Display on the device: shows the current power and the total meter reading
- Fail-safe: detects grid failures immediately via dual DC/AC power supply
- Flexible choice: adapts to your installation – configurable primary currents up to 1999 A (at 1 A secondary) or 9999 A (at 5 A secondary)
- Bidirectional energy measurement
Note
Matching current transformers are required: 5A current transformer 400A 35mm or 5A current transformer 200A 24mm.
Supply and power
| Voltage | AC / voltage inputs (mains)24 VDC input100 … 480 VAC, 50/60 Hz10 … 30 VDC |
|---|---|
| Current | 4 mA8 mA |
| Power consumption | <= 0.6 W< 0.2 W |
| Power loss at max. load | <= 2 W0.3 W |
Measuring range
| Power | Range: 0.01 … 999.9 kW / kVAr / kVA Accuracy: ± 1 % |
|---|---|
| Energy | Range: 0 … 999999.9 kWh / kVArh Consumption and delivery Accuracy: class 2 IEC 62053, Class C EN 50470 |
| Voltage | Range: 100 … 277 VAC Accuracy: ± 0.5 % |
| Current | Range: 0.05 … 6 A Accuracy: ± 0.5 % |
| Frequency | Range: 45 … 60 Hz Accuracy: ± 0.2 % |
| Supported primary current | 1 … 1 999 A at 1 A secondary, 5 … 9 999 A at 5 A secondary |
Operating conditions – according to MID 2014/32/EU Annex V
| Voltage | Un: 3×230 / 400 VAC, ± 20 % |
|---|---|
| Current | Imin: 0.05 A / Iref: 5 A / Imax: 6 A |
| Frequency | fn: 50 Hz, ± 2 % |
| Power factor | cos: 0.5 inductive … 0.8 capacitive |
| Accuracy (energy) | Class C (0.5 %, @ +5 °C … +30 °C) |
Interfaces
| LOXONE Tree | Connection to Miniserver / Tree Extension |
|---|
Ambient conditions
| Temperature | -40 … 70°C / -40 … 158°F |
|---|---|
| Humidity | max. 90 % RH (non-condensing) |
| Degree of protection | IP20 |
Terminals
| Terminal type | Current & voltage inputs24 VDC & LOXONE Tree-DG220B |
|---|---|
| Conductor cross-section | 0.5 … 1.5 mm² / AWG 22 … 14 Wire end ferrules required for fine-stranded conductors0.28 … 0.8 mm² / AWG 23 … 18 |
| Stripping length | 6 … 7 mm / 0.24 … 0.28”5 … 6 mm / 0.2 … 0.24" |
| Tightening torque | 0.6 Nm / 0.44 lbf·ft- |
| Temperature resistance | -40 … 70 °C / -40 … 158 °F-40 … 105 °C / -40 … 221 °F |
| Slotted screwdriver | 0.5 × 3.5 mm- |
Wiring diagram

Product properties
| Mounting type | DIN rail according to EN 50022, 35 mm |
|---|---|
| Colour | Black: RAL 9005 |
| Gloss level | Matt |
Weight & dimensions
| Net weight | 168 g |
|---|---|
| Gross weight | 190 g |
| Product dimensions | 36 x 100 x 66 mm / 2.83 x 3.64 x 2.60" (L x W x H), 2 modules |
| Package dimensions | 120 x 70 x 40 mm / 4.72 x 2.76 x 1.57" (L x W x H) |
Product dimension drawing
Certifications & standards
| Accuracy class 0.5 | Accuracy class 0.5 |
|---|